Page 63 - Hilti (HK) – Product Catalogue
P. 63
Drop-in (flush) anchor HKD
BASE MATERIALS Approvals
● Concrete (uncracked) ETA 02/0032 for HKD drop-in anchor (ETAG 001-04,
ETA
Option 7)
ETA 06/0047 for HKD drop-in anchor multiple
APPLICATIONS ETA, Fire resistance
applications (ETAG 001-06, Option -)
● For medium-duty loads with anchor bolts and threaded rods, Approvals and test reports may apply to selected products only. Please refer
e.g. suspension systems for pipes, air ducts, sprinkler systems, to the documents for details.
etc.
● For redundant applications in cracked concrete or single-point
applications in uncracked concrete
ADVANTAGES
● Features a lip for flush setting, regardless of hole depth
● Shallow drilling depth (25mm), available in M6, M8, M10 and
M12 sizes
● Visual check for correct setting when used with Hilti manual
setting tool
Technical data
Material composition (Galvanized) Steel, zinc-plated (min.
5 μm);
(Sherardized) Steel, zinc-plated
(min.
45 μm);
(Stainless steel) Steel, A4 (SS316) These are abbreviated instructions which may vary according to the application.
Head configuration Inner thread
Type of fastening Pre-fastening
Approvals / test reports ETA, Fire, FM (Factory Mutual)
Suitable for cracked concrete Yes
with redundant fastenings
Recommended load (kN), non-cracked concrete at 25N/mm², safety factor(γ)=3
M6x25/ M8x30/ M10x40/ M12x50/ M16x65/
Model Size M20x80
1/4”x25 5/16”x30 3/8”x40 1/2”x50 5/8”x65
Tensile Load, Nrec 2.1 2.8 4.3 5.9 8.8 12.0
HKD
Shear Load, Vrec 1.7 2.9 3.7 6.1 11.3 16.3
HKD- Tensile Load, Nrec 2.1 2.8 4.3 5.9 8.8 12.0
SR/
HKD-ER Shear Load, Vrec 2.1 2.8 3.5 6.2 10.7 17.0
Remarks:
1) All the data applies to no edge distance, spacing and other influences
2) For detail design method, please refer to Fastening Technology Manual
Hilti online: www.hilti.com.hk
299